Filter material ECOMIX P 25 l

Ecomix® P is a high performance filter media for difficult water.
Description ...

150.00 €
Compare products

Loading Ecomix® P:
removes plaque on plumbing and scale on heating elements;
removes the metallic taste of water;
will get tired of the unpleasant smell of water.

Main advantages:
- Solving the main problems of water in one filter, instead of 2-
- Stable quality of purified water throughout the entire service life.
- Low salt consumption for regeneration.

Where is it used?
Ecomix® P is used in Ecosoft FK type household and industrial filters. Ecomix is ​​loaded into the filter as a mixture and is divided into 4 layers during the first regeneration. For regeneration, ordinary tableted salt is used.

Active components of Ecomix® filter media:
1. Inert material - improves backwash.
2. FerroSorb sorbent reduces iron and manganese content.
The mechanism for reducing the iron content consists of adsorption (fixation) on the surface of the material, oxidation, formation of an active layer, and autocatalytic oxidation. As a result, the content of all the main forms of iron decreases: dissolved, oxidized, organic and colloidal.
The best iron and manganese removal efficiencies are obtained by pumping water from the well directly to the Ecomix material.
3. Ion exchange resin (cation resin) - softens water.
In the process of filtering water through a cation exchanger, the hardness ions Ca2 + and Mg2 + are replaced by Na + ions. During regeneration, calcium and magnesium ions are washed off into the drainage, and the cation exchanger is saturated with sodium ions from the saline solution.
4. Quartz sand is used to evenly distribute the flow of water through the filter media during flushing.

Regeneration of Ecomix® filter media:
In the course of operation, the filter material is periodically regenerated with a salt solution, just like a conventional ion exchange resin.

- Calcium and magnesium ions are replaced with sodium ions in the brine regeneration step.
- Iron and manganese compounds are removed by surface friction of FerroSorb grains in the fluidized bed during backwashing.

Maximum operating temperature: 40 ° C
Filtration rate: 20-25 m / h
Backwash speed: 10-15 m / h
Brine rinsing speed: 3-5 m / h

Minimum layer height: 500 mm
Optimum layer height: 800 mm
Free volume: more than 40%
Salt consumption: 100 g / l of material
Brine concentration: 8-10%
Water consumption for flushing: less than 10 l / l of material
Working exchange capacity for hardness salts: 0.8 g-eq / l